Datwyler Data-R LSOH

Round data bus cable FR/LSOH, Euroclass Dca

1 Conductor: solid
2 Shielding: Alu-laminated plastic foil with drain wire
3 Sheath: FRNC/LS0H

Description

Special bus cable for the decentralised Datwyler EIB system for installation in dry rooms with medium mechanical requirements. The cable can also be used in areas with explosion risk and run through damp and wet rooms. This cable type is not suitable for outdoor applications. Max. permitted temperature at conductor is 70°C.De kabel kan ook worden gebruikt in zones met explosiegevaar en kan lopen door vochtige en natte ruimtes.Dit type kabel is niet geschikt voor buitentoepassingen.Max. toegestane temperatuur aan de geleider is 70 ° C.
Copper conductor:Bare copper wire, 0.8 mm diameter
Core insulation:Polyolefin compound EN 50290.2.23 ”L/MD“
Stranding:4 cores to star quad
Tape:Polyester tape
Shielding:Aluminium laminated plastic foil with drain wire, 0.8 mm diameter
Outer sheath:Green
Imprint:EIB BUS LSOH J-2Y(St)H N x N x 0,8 MM
„production date“ „meter marks“
Nominal voltage:max. 300 V
Test voltage:4000 V, 50 Hz
Operating temperaturepermanent installation:-30°C to +70°C
 during installation:-5°C to +50°C

Reaction to fire (Euroclass)

EN 13501-6: Dca

Zero alogeni, no gas corrosivi

IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2

Propagazione delle fiamme

IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2

Diffusione delle fiamme

IEC 60332-3-25 Cat.D, EN 60332-3-25 cat.D, VDE 0482-332-3 cat.D (for FR/LSOH)

Densità del fumo

IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2

Documentation

ENDENLFRCNESIT
Product Datasheet

Versions

Article No.Dimensioni n x p x [mm]Base CuDoPReaction to fire (Euroclass)Numero di coreGuaina Ø [mm]Peso [kg/km]Tasso di Cu [kg/km]PU
18106302DK1 x 2 x 0.8100Dca-s2,d2,a12644151000 m tamburo
18106402DK2 x 2 x 0.8100Dca-s2,d2,a12760251000 m tamburo