CU 7080 4P / 2x4P F8
Data cable, S/FTP, Category 7, AWG23, Euroclass B2ca

1 Inner Conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.4 Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH Orange RAL 2003












Description
Excellent shielding effect due to individually screened pairs and overall copper braid.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class F applications (600 MHz) in accordance with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV) in accordance with IEC 15018.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE up to 100W.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class F applications (600 MHz) in accordance with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV) in accordance with IEC 15018.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE up to 100W.

Category | 5e | 6 | 6A | 7 | ||||||
Frequency [MHz] | 1 | 4 | 10 | 100 | 250 | 500 | 600 | 800 | 862 | 1200 |
Attenuation [dB/100m] | 1.9 | 3.6 | 5.6 | 17.9 | 28 | 41 | 46 | 52 | 54 | 63 |
NEXT [dB] | 100 | 100 | 100 | 100 | 100 | 92 | 90 | 84 | 83 | 80 |
PS NEXT [dB] | 97 | 97 | 97 | 97 | 97 | 89 | 87 | 81 | 80 | 77 |
ACR-N [dB] | 98 | 96 | 94 | 82 | 72 | 51 | 44 | 32 | 29 | 17 |
PS-ACR-N [dB] | 95 | 93 | 91 | 79 | 69 | 48 | 41 | 29 | 26 | 14 |
ACR-F [dB] | 98 | 98 | 98 | 78 | 69 | 56 | 45 | 39 | 37 | 28 |
PS-ACR-F [dB] | 95 | 95 | 95 | 75 | 66 | 53 | 42 | 36 | 34 | 25 |
Return loss [dB] | 26 | 30 | 33 | 33 | 28 | 26 | 25 | 23 | 22 | 18 |
These performance data are typical measured values. |
Category: | Cat.7 |
Coupling attenuation: | 85 dB |
Delay Skew: | 12 ns/100 m |
Impedance at 100 MHz, ±5Ω: | 100 Ω |
Loop resistance at 20°C: | < 140 Ω/km |
Near end unbalance attenuation LCL at 1-600 MHz: | 40 dB |
NVP %: | 81 |
operating capacity: | 42 pF/m |
Transfer impedance 1/10/30 MHz: | < 6/6/10 mΩ/m |
Supported applications
10Base-T, 100Base-T, 1000Base-T, 2.5GBase-T, 5GBase-T, 10GBase-T, Fieldbus
Mechanical properties
Minimum bending radius during installation: | 60 mm |
Minimum bending radius permanently installed: | 30 mm |
Tensile strength (4P): | 110 N |
Tensile strength (2x4P): | 220 N |
Minimal crush resistance / 10cm: | 1,000 N |
Minimum number of impacts: | 10 |
Installation temperature: | 0 °C - +50 °C |
Operating temperature: | -20 °C - +60 °C |
Reaction to fire (Euroclass)
EN 13501-6: B2caWire colour
white/bluewhite/orangewhite/greenwhite/brownin accordance with IEC 60189 and IEC 60708Imprint
DATWYLER «cable type» «additional text» «batch number» «meter marks»Zero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SAFlame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1Flame spread
IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SDPoE
IEEE 802.3btEMC
shieldedSegregation class
dCat./Class
Cat 7 / Class F - limit values as specified by IEC 61156-5 and EN 50288-4-1 guaranteedDocumentation
Versions
Related products
KS-T Plus 1/8 tool-less Cat.6A (IEC)
RJ45 module, shielded, Category 6A (IEC)
KS-TC Plus Cat.6A (IEC) tool-less, compact
RJ45 module, shielded, Category 6A (IEC)