CU 5002 4P Dca
Data cable, F/UTP, Category 5e, AWG24, Euroclass Dca

1 Inner conductor: AWG24 Bare copper wire
2 PE insulated conductor: 1.0 mm Ø, PE Foam Skin
3 Drain wire: Tinned copper wire
4 Polyester foil
5 Overall screen: Alu Polyester foil
6 Outer sheath: FRNC/LS0H orange RAL 2003










Description
Excellent shielding effect due to overall screen foils.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class D applications (100 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class D applications (100 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+.

Category | 5e | ||||
Frequency [MHz] | 1 | 4 | 10 | 100 | 250 |
Attenuation [dB/100m] | 1.9 | 3.6 | 5.6 | 18.2 | 29 |
NEXT [dB] | 75 | 70 | 65 | 44 | 40 |
PS NEXT [dB] | 72 | 67 | 62 | 41 | 37 |
ACR-N [dB] | 73 | 66 | 59 | 26 | 11 |
PS-ACR-N [dB] | 70 | 63 | 56 | 23 | 8 |
ACR-F [dB] | 84 | 69 | 63 | 41 | 31 |
PS-ACR-F [dB] | 81 | 66 | 60 | 38 | 28 |
Return loss [dB] | 27 | 31 | 31 | 28 | 24 |
These performance data are typical measured values. |
Category: | Cat.5e |
Coupling attenuation: | 40 dB |
Delay Skew: | 8 ns/100 m |
Impedance at 100 MHz, ±5Ω: | 100 Ω |
Loop resistance at 20°C: | < 155 Ω/km |
Near end unbalance attenuation LCL at 1-600 MHz: | 40 dB |
NVP %: | 76 |
operating capacity: | 43 pF/m |
Transfer impedance 1/10/30 MHz: | < 45/90/190 mΩ/m |
Supported applications
10Base-T, 100Base-T, 1000Base-T, Fieldbus
Mechanical properties
Minimum bending radius during installation: | 48 mm |
Minimum bending radius permanently installed: | 24 mm |
Tensile strength (4P): | 91 N |
Minimal crush resistance / 10cm: | 1,000 N |
Minimum number of impacts: | 10 |
Installation temperature: | 0 °C - +50 °C |
Operating temperature: | -20 °C - +60 °C |
Reaction to fire (Euroclass)
EN 13501-6: DcaWire colour
white-blue/bluewhite-orange/orangewhite-green/greenwhite-brown/brown(with longitudinal stripes)in accordance with IEC 60189 and IEC 60708Imprint
DATWYLER «cable type» «additional text» «batch number» «meter marks»Zero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SAFlame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD - applies to FRNC/LS0HPoE
IEEE 802.3afEMC
shieldedSegregation class
bCat./Class
Cat 5e / Class D - limit values as specified by IEC 61156-5 and EN 50288-2-1 guaranteedDocumentation