JE-H(St)HRH...Bd FE180 E30-E90 fire alarm
Fire alarm cable with steel wire braiding, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, halogen-free
3 Drain wire: copper, Ø 0.8 mm
4 Inner covering: plastic tape, halogen-free
5 Shielding: Al-laminated plastic foil, halogen-free
6 Inner sheath: FRNC/LS0H
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LS0H






Description
Permitted operating temperature at conductor of +70°C.
Conductor | Bare copper, solid, 0.8 mm diameter, VDE 0815 |
Insulation | Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-26 |
Core colours | According to VDE 0815, bundles identified by numbered tape |
Separator | PETP “Plastic Tape” |
Shielding | Al-laminated tape with copper drain wire Ø 0.8 mm |
Inner sheath | Flame retardant polyolefin compound, VDE 0819 part 107, EN 50290-2-27 and VDE 0250-214 “HM2“ |
Armouring | Galvanised steel wire braid |
Outer sheath | Flame retardant polyolefin compound, VDE 0819 part 107, EN 50290-2-27 and VDE 0250-214 “HM 2“ |
Sheath colour | Red |
Insulation resistance | minimum 100 MΩ x km |
Loop resistance | maximum 73.2 Ω/km at 0.8 mm |
Capacitance unbalance | maximum 120 nF/km at 800 Hz |
Capacitance coupling | K maximum 200 pF/100m at 800 Hz |
Rated voltage | maximum 225 V |
Test voltage | 500 V, 50 Hz Core/Core |
2000 V, 50Hz, Core/Screen |
Mechanical properties
Minimum bending radius | 7.5 x D (D = outer diameter) | |
Crush resistance | ≥ 1000 N/10 cm | |
Impact | ≥ 10 impacts | |
Operating temperature | permanent installation | -30°C to +70°C |
during installation | -5°C to +50°C |
Note
System Circuit Integrity dependent on installation method.
Zero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SAFlame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1Flame spread
IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SDCircuit Integrity (FE180)
IEC 60331-11/-21 (180 minutes), VDE 0472 part 814 (FE180), IEC 60331-1, IEC 60331-2 (120 minutes ), EN 50200, VDE 0482-200 (PH120) and EN 50362, VDE 0482-362 (120 minutes), BS 6387 C/W/Z, AREI-RGIE Art.104-FR1System circuit integrity
DIN 4102 part 12, AREI-RGIE Art.104-FR2Documentation
Versions
Article No. | Product | Number of Pairs | Number of Cores | Diameter [mm] | Sheath colour | Sheath Ø [mm] | Weight [kg/km] | Cu rate [kg/km] | Fire load [kWh/m] | PU |
---|---|---|---|---|---|---|---|---|---|---|
18811900ZZ | JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm | 2 | 2 | 0.8 | red | 9.3 | 125 | 25 | 0.26 | by the metre |
188120 | JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0.8 mm | 4 | 2 | 0.8 | red | 12 | 194 | 45 | 0.39 | by the metre |
188127 | JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0.8 mm | 8 | 2 | 0.8 | red | 18.2 | 418 | 85 | 0.93 | by the metre |
188128 | JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0.8 mm | 12 | 2 | 0.8 | red | 19.1 | 489 | 126 | 1.01 | by the metre |
188129 | JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0.8 mm | 20 | 2 | 0.8 | red | 22.5 | 679 | 206 | 1.32 | by the metre |
188346 | JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0.8 mm | 32 | 2 | 0.8 | red | 26.7 | 911 | 326 | 1.72 | by the metre |
Additional dimensions available on request.
Related products
(N)HXH FE180 E30-E60
Safety cable, 0.6/1kV, Keram
(N)HXCH FE180 E30-E60
Safety cable, 0.6/1kV, Keram
(N)HXH CL FE180 E30-E60
Safety cable, 0.6/1kV armoured with rodent protection, Keram