N2XCH
Safety cable, 0.6/1kV, Euroclass Cca
halogen-free, with improved fire characteristics,
CENELEC HD 604 S1, VDE 0276-604

1 Conductor: solid/ stranded
2 Insulation: cross-linked PE, zero halogen
3 Filler: flame retardant, zero halogen
4 Concentric conductor: bare copper wire
5 Reinforcing helix: bare copper tape
6 Separator: plastic tape
7 Sheath: FRNC/LSZH









Description
The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Conductor: | Bare copper, solid or stranded, IEC 60228, EN 60228, (VDE 0295) |
Insulation: | Cross-linked Polyethylene, CENELEC HD 604 S1, VDE 0276-604 |
Filler: | Halogen-free compound or plastic tape |
Concentric conductor: | Bare copper wires with reinforced helix |
Separator: | Plastic tape |
Outer sheath: | Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 “HM4” |
Core colours: | CENELEC HD 308 S2 and VDE 0293 |
Sheath colour: | Black |
Imprint: | On request |
Nominal voltage: | 0.6/1kV | |
Test voltage: | 4000V, 50Hz |
Mechanical properties
Minimum bending radius | during and permanent installation: | 12 x D (multicore cable) |
(D = outer diameter) | ||
Operating temperature | permanent installation: | -45°C to +90°C |
during installation: | -5°C to +50°C |
Reaction to fire (Euroclass)
EN 13501-6: CcaZero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SAFlame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1Flame spread
IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SDDocumentation
Versions
Article No. | Product | Reaction to fire (Euroclass) | Number of Cores | Cross section [mm²] | Sheath Ø [mm] | Weight [kg/km] | Cu rate [kg/km] | Fire load [kWh/m] | Construction | Conductor | PU |
---|---|---|---|---|---|---|---|---|---|---|---|
17017204CZ | N2XCH 3 x 50/25 | Cca-s1,d1,a1 | 3 | 50/25 | 29 | 1990 | 1723 | 2.72 | 3L | solid | by the metre |
17017504CZ | N2XCH 3 x 70/35 | Cca-s1,d1,a1 | 3 | 70/35 | 34.8 | 2830 | 2410 | 4.11 | 3L | stranded | by the metre |
17019704CZ | N2XCH 3 x 95/50 | Cca-s1,d1,a1 | 3 | 95/50 | 37.7 | 4350 | 3296 | 4.60 | 3L | stranded | by the metre |
17017404CZ | N2XCH 3 x 120/70 | Cca-s1,d1,a1 | 3 | 120/70 | 41.6 | 5271 | 4236 | 5.55 | 3L | stranded | by the metre |
17019804CZ | N2XCH 3 x 150/70 | Cca-s1,d1,a1 | 3 | 150/70 | 45.6 | 5450 | 5100 | 6.68 | 3L | stranded | by the metre |
17018404CZ | N2XCH 4 x 50/25 | Cca-s1,d1,a1 | 4 | 50/25 | 34.4 | 2600 | 2203 | 3.38 | 3LN | stranded | by the metre |
17018504CZ | N2XCH 4 x 70/35 | Cca-s1,d1,a1 | 4 | 70/35 | 40.5 | 3550 | 3082 | 4.48 | 3LN | stranded | by the metre |
17018604CZ | N2XCH 4 x 95/50 | Cca-s1,d1,a1 | 4 | 95/50 | 44.4 | 4800 | 4208 | 5.44 | 3LN | stranded | by the metre |
17018704CZ | N2XCH 4 x 120/70 | Cca-s1,d1,a1 | 4 | 120/70 | 48.3 | 6500 | 5382 | 6.38 | 3LN | stranded | by the metre |
17018804CZ | N2XCH 4 x 150/70 | Cca-s1,d1,a1 | 4 | 150/70 | 53.2 | 7950 | 6540 | 7.97 | 3LN | stranded | by the metre |
17018904CZ | N2XCH 4 x 185/95 | Cca-s1,d1,a1 | 4 | 185/95 | 58.9 | 9970 | 8159 | 9.86 | 3LN | stranded | by the metre |