FE5-CL
Safety cable, 0.6/1kV, armoured with rodent protection, euroclass Dca
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5. H

1 Conductor: solid/stranded
2 Insulation: cross-linked PE, zero halogen
3 Inner sheath: Polyolefin, flame retardant, zero halogen
4 Armouring: galvanised steel tape
5 Sheath: FRNC/LSZH








Description
The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90°C.
Conductor | Bare copper, solid or stranded, IEC 60228, EN 60228 |
Insulation | Cross-linked Polyethylene CENELEC HD 604 S1 part 5 sec. H |
Inner sheath | Flame retardant Polyolefin compound CENELEC HD 604 S1 part 5 sec. H |
Armouring/rodent protection | Single core cable with copper tape (CLCU) and |
Multicore cable with galvanised steel tape (CL) | |
Outer sheath | Flame retardant Polyolefin compound CENELEC HD 604 S1 part 5 sec. H |
Core colours | CENELEC HD 308 S2 |
Sheath colour | Black |
Nominal voltage | 0.6/1kV |
Test voltage | 3500V, 50Hz |
Mechanical properties
Minimum bending radius | during and permanent installation | 15* x D (single core cable) |
12* x D (multicore cable) | ||
(D = outer diameter) | ||
Operating temperature | permanent installation | -45°C to +90°C |
during installation | -5°C to +50°C |
Note
Additional dimensions available on request.
Reaction to fire (Euroclass)
EN 13501-6: DcaZero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SAFlame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1Flame spread
IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SDDocumentation