FO Universal ZGGFR Safety / U-DQ(ZN)BH
Safety cable E30*, up to 12 fibres
metal-free, water resistant, rodent protection,
in accordance with IEC 60332-1-2 and IEC 60332-3-24
30 minutes System Circuit Integrity* with reference to DIN 4102-12

1 ≤ 12 fibres
2 Flame retardant protective coating
3 Glass armour
4 Ripcord
5 FR/LS0H sheath





Description
The optimal combination of flame retardant fibre coating and flame-inhibiting stabilizing elements ensures enhanced functional integrity (System Circuit Integrity*) in case of fire for 30 minutes (transmission of audio, video and 1Gbit/s signals approved by a certified test report).
Safety applications in tunnels, underground railways, banks, insurance companies, large-scale industry.
LAN backbone.
Indoor and outdoor cabling.
Can also be installed in cable platforms, trays, ducts and vertical shafts (without System Circuit Integrity*).
Can be spliced in FO distributors.
LAN backbone.
Indoor and outdoor cabling.
Can also be installed in cable platforms, trays, ducts and vertical shafts (without System Circuit Integrity*).
Can be spliced in FO distributors.
Optical properties
The cables are available with different types of optical fibre (see fibre data sheets).
Mechanical properties
Temperature range | storage: | -25 / +70°C | IEC 60794-1-22 F1 |
during installation: | -10 / +50°C | ||
in operation: | -25 / +60°C | ||
Tensile performance: | IEC 60794-1-21 E1 | ||
Crush resistance: | IEC 60794-1-21 E3 | ||
Impact: | IEC 60794-1-21 E4 | ||
Repeated bending: | IEC 60794-1-21 E6 | ||
Torsion: | IEC 60794-1-21 E7 | ||
Bend: | IEC 60794-1-21 E11 | ||
Water penetration: | IEC 60794-1-22 F5 |
Note
* System Circuit Integrity is dependent on installation method. Certified clamps, ducts, conduits, etc. are mandatory.
UV resistance
EN 50289-4-17:2015 (UVA-340)Reaction to fire (Euroclass)
not classifiedImprint
DATWYLER «cable type» «Datwyler designation» «DIN designation» «no. of fibres» «fibre type» «add. text» «batch no.» «meter marks»Zero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2Flame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2Flame spread
IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2Circuit Integrity
IEC 60331-11, IEC 60331-25 (FE90), EN 50200 PH90, VDE 0482-200System circuit integrity
according to DIN 4102 part 12, VKF Fire Safety Application No. 24176Documentation
Versions
Article No. | Product | Number of fibres | Loose Tubes | Sheath colour | Fibre type | Sheath Ø [mm] | Weight [kg/km] | Bending radius [mm] | Tensile load [N] | Crush resistance continuous [N] | Crush resistance short term [N] | Fire load [kWh/m] | PU |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
187288 | FO Universal Safety 1x4 | 4 | 1 | red | E9/125 G.652.D OS2 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
190604 | FO Universal Safety 1x4 | 4 | 1 | red | G50/125 OM3 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
193447 | FO Universal Safety 1x4 | 4 | 1 | red | G50/125 OM4 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
191867 | FO Universal Safety 1x6 | 6 | 1 | red | E9/125 G.652.D OS2 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
191851 | FO Universal Safety 1x6 | 6 | 1 | red | G50/125 OM3 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
193448 | FO Universal Safety 1x6 | 6 | 1 | red | G50/125 OM4 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
196130 | FO Universal Safety 1x8 | 8 | 1 | red | E9/125 G.652.D OS2 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
196120 | FO Universal Safety 1x8 | 8 | 1 | red | G50/125 OM3 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
193449 | FO Universal Safety 1x8 | 8 | 1 | red | G50/125 OM4 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
190719 | FO Universal Safety 1x12 | 12 | 1 | red | E9/125 G.652.D OS2 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
191796 | FO Universal Safety 1x12 | 12 | 1 | red | G50/125 OM3 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
193450 | FO Universal Safety 1x12 | 12 | 1 | red | G50/125 OM4 | 7.8 | 75 | 120 | 1000 | 2000 | 5000 | 0.301 | by the metre |
Related products
FO Universal DLTS ZGGFR / U-BQ(ZN)BH
up to 24 fibres, Euroclass Dca
FO Universal DLTS ZGGFR / U-BQ(ZN)BH
up to 24 fibres, Euroclass Cca
FO Universal DLTS ZGGFR / U-BQ(ZN)BH
up to 24 fibres, Euroclass B2ca
More information