CU 7150 4P / 2x4P F8 Multimedia
Data cable, S/FTP, Category 7A, AWG22, Euroclass B2ca

1 Inner conductor: AWG22 Bare copper wire
2 PE insulated conductor: 1.6 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH orange RAL 2003













Description
Excellent shielding effect due to individually screened pairs and overall copper braid.
Easy identification of wires thanks to longitudinal colour markings.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Data cable for structured premises cabling. For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Optimized for the transmission of broadband signals (such as cable TV) in accordance with IEC 15018.
Due to the increased wire section eminently suited for Power over Ethernet (PoE) / PoE+.
Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Optimized for the transmission of broadband signals (such as cable TV) in accordance with IEC 15018.
Due to the increased wire section eminently suited for Power over Ethernet (PoE) / PoE+.

Category | 5e | 6 | 6A | 7 | CATV | 7A | 61156-7 | ||||
Frequency [MHz] | 1 | 4 | 10 | 100 | 250 | 500 | 600 | 862 | 1000 | 1200 | 1500 |
Attenuation [dB/100 m] | 1.7 | 3.2 | 4.9 | 16.2 | 26 | 38 | 40 | 49 | 54 | 58 | 68 |
NEXT [dB] | 103 | 103 | 103 | 103 | 103 | 98 | 96 | 92 | 90 | 85 | 80 |
PS NEXT [dB] | 100 | 100 | 100 | 100 | 100 | 95 | 93 | 89 | 87 | 82 | 77 |
ACR-N [dB] | 101 | 100 | 98 | 87 | 77 | 60 | 56 | 43 | 36 | 27 | 12 |
PS-ACR-N [dB] | 98 | 97 | 95 | 84 | 74 | 57 | 53 | 40 | 33 | 24 | 9 |
ACR-F [dB] | 110 | 108 | 106 | 94 | 84 | 71 | 66 | 58 | 55 | 46 | 41 |
PS-ACR-F [dB] | 107 | 105 | 103 | 91 | 81 | 68 | 63 | 55 | 52 | 43 | 38 |
Return loss [dB] | 26 | 30 | 33 | 33 | 28 | 26 | 25 | 24 | 23 | 23 | 20 |
These performance data are typical measured values. |
Category: | Cat.7A |
Coupling attenuation: | 85 dB |
Delay Skew: | 17 ns/100 m |
Impedance at 100 MHz, ±5Ω: | 100 Ω |
Loop resistance at 20°C: | < 111 Ω/km |
Near end unbalance attenuation LCL at 1-600 MHz: | 40 dB |
NVP %: | 80 |
operating capacity: | 41 pF/m |
Transfer impedance 1/10/30 MHz: | < 5/5/8 mΩ/m |
Mechanical properties
Minimum bending radius during installation: | 64 mm |
Minimum bending radius permanently installed: | 32 mm |
Tensile strength (4P): | 130 N |
Tensile strength (2x4P): | 260 N |
Minimal crush resistance / 10cm: | 1,000 N |
Minimum number of impacts: | 10 |
Installation temperature: | 0 °C - +50 °C |
Operating temperature: | -20 °C - +60 °C |
Reaction to fire (Euroclass)
EN 13501-6: B2caWire colour
white-blue/bluewhite-orange/orangewhite-green/greenwhite-brown/brown(with longitudinal stripes)in accordance with IEC 60189 and IEC 60708Imprint
DATWYLER «cable type» «additional text» «batch number» «meter marks»Zero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SAFlame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1Flame spread
IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2Smoke density
IEC 61034-1/-2, EN 61034-1/-2 , VDE 0482-1034-1/-2, AREI-RGIE Art.104-SDPoE
IEEE 802.3btEMC
shieldedSegregation class
dCat./Class
Cat 7A / Class FA - limit values as specified by IEC 61156-5, IEC 61156-7 and EN 50288-9-1 guaranteedDocumentation
Versions
Related products
KS-TC Plus Cat.6A (IEC) tool-less, compact
RJ45 module, shielded, Category 6A (IEC)