CU 696 4P
Data cable, UTP, Category 6A, AWG23, Euroclass Cca

1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.3 mm Ø
3 Alien Crosstalk barrier
4 Outer sheath: FRNC/LS0H










Description
Robust cable design with reliable electrical performance thanks to Alien Crosstalk barrier.
Compatible with all current connecting hardware in accordance with EN 50173-1 and ISO/IEC 11801-1.
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class EA applications (500 MHz) in accordance with EN 50173-1 and ISO/IEC 11801-1.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class EA applications (500 MHz) in accordance with EN 50173-1 and ISO/IEC 11801-1.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE.
Category | 5e | 6 | 6A | |||
Frequency [MHz] | 1 | 4 | 10 | 100 | 250 | 500 |
Attenuation [dB/100m] | 2.1 | 3.8 | 5.9 | 19 | 30 | 43 |
NEXT [dB] | 93 | 93 | 93 | 93 | 83 | 75 |
PS NEXT [dB] | 90 | 90 | 90 | 90 | 80 | 72 |
ACR-N [dB] | 91 | 89 | 87 | 73 | 53 | 32 |
PS-ACR-N [dB] | 88 | 86 | 84 | 70 | 50 | 29 |
ACR-F [dB] | 96 | 96 | 96 | 74 | 56 | 33 |
PS-ACR-F [dB] | 93 | 93 | 93 | 71 | 53 | 30 |
Return loss [dB] | 26 | 28 | 30 | 30 | 27 | 21 |
These performance data are typical measured values. |
Category: | Cat.6A |
Coupling attenuation: | 55 dB |
Delay Skew: | 5 ns/100 m |
Impedance at 100 MHz, ±5Ω: | 100 Ω |
Loop resistance at 20°C: | < 150 Ω/km |
Near end unbalance attenuation LCL at 1-600 MHz: | 40 dB |
NVP %: | 79 |
operating capacity: | 42 pF/m |
Transfer impedance 1/10/30 MHz: | < 50/100/200 mΩ/m |
Supported applications
10Base-T, 100Base-T, 1000Base-T, 2.5GBase-T, 5GBase-T, 10GBase-T, Fieldbus
Mechanical properties
Minimum bending radius during installation: | 56 mm |
Minimum bending radius permanently installed: | 28 mm |
Tensile strength (4P): | 95 N |
Tensile strength (2x4P): | 190 N |
Minimal crush resistance / 10cm: | 1,000 N |
Minimum number of impacts: | 10 |
Installation temperature: | 0 °C - +50 °C |
Operating temperature: | -20 °C - +60 °C |
Reaction to fire (Euroclass)
EN 13501-6: CcaWire colour
white/blue white/orange white/green white/brown in accordance with IEC 60189 and IEC 60708Imprint
DATWYLER «cable type» «additional text» «batch number» «meter marks»Zero halogen, no corrosive gases
IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SAFlame propagation
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1Smoke density
IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SDPoE
IEEE 802.3btEMC
unshieldedSegregation class
cCat./Class
Cat.6A / Class EADocumentation
Versions
Related products
CU 8203 4P
Data cable, S/FTP, Category 8.2, AWG23, Euroclass Dca
CU 8203 4P
Data cable, S/FTP, Category 8.2, AWG23, Euroclass Cca
CU 8203 4P
Data cable, S/FTP, Category 8.2, AWG23, Euroclass B2ca